IEC 60870-5-104 telecontrol intrusion detection for Craton Shield (IEC 62443).

Overview

Monitors IEC 60870-5-104 traffic for security anomalies in SCADA and telecontrol systems. Designed for RTUs, gateways, and control centres.

MSRV: 1.82 | Environment: #![no_std], zero heap allocation

Features

  • TypeID allowlist -- 256-bit bitmask restricting permitted ASDU type identifiers
  • COT filtering -- Cause of Transmission filtering rejects frames with unexpected COT values
  • Write protection -- block command TypeIDs (45--51, 58--64) when rule is read-only
  • I-frame sequence tracking -- forward-progress window detects replays and large gaps
  • Rate limiting -- per-TypeID token bucket with LRU eviction

Stack Budget

~500 bytes

Usage

use vs_iec60870_monitor::{Iec60870Monitor, Iec60870Frame, Iec60870FrameFormat, Iec60870Cot};

let mut monitor = Iec60870Monitor::new_strict();
monitor.add_rule(1, true, 20).unwrap(); // ASDU addr 1, read-only, 20 req/s
monitor.set_type_id_allowlist(1, true); // Allow M_SP_NA_1

let result = monitor.inspect(&frame);
if !result.allowed {
    // frame was blocked
}

License

Apache-2.0. See LICENSE.